Strip Foundation

EN 1997-1

Checks a strip foundation for bearing pressure and sliding to EN 1997-1.

Diagram

B = 600 mmD=500mmqa = 150 kN/m²

Example inputs

Strip width B600 mm
Foundation depth D500 mm
Wall load — ULS (wEd)80 kN/m
Wall load — characteristic55 kN/m
Allowable bearing (qa)150 kN/m²
Concrete gradeC25/30
National annexUK

Results

Strip Foundation — 600mm wide

C25/30 · depth 500mm · qa=150 kN/m² · EN 1997-1

Results

Bearing PASS
util 0.69104.17EN 1997-1 §6.5
Strip width B0.6m
Self-weight = B × D × γc7.5kN/m
Total characteristic load = Fchar + Wsw62.5kN/m
σ gross bearing pressure = N_total / B104.17kN/m²EN 1997-1 §6.5
qa allowable bearing150kN/m²
Base Bending PASS
util 0.012.41EN 1992-1-1 §6.1
Cantilever length lc = (B − wall) / 2192.5mm
pULS upward pressure (ULS) = wEd / B0.13N/mm²
d effective depth = D − cover − φ/2442mm
mEd base moment = pULS × lc² / 22.41kNm/mEN 1992-1-1 §6.1
K bending parameter = mEd / (fcd × b × d²)0.001
z lever arm = d[0.5 + √(0.25 − K/1.134)]419.9mm
As,req reinforcement = mEd / (fyd × z)13.2mm²/mEN 1992-1-1 §6.1
Min. Depth PASS
util 1.00500.00EN 1997-1 §6.4
Foundation depth D500mm
Minimum depth requirement500mmEN 1997-1 §6.4